 RCM-SS
Six-Relay Addressable Control Module
Description
Gamewell's SmartScanTM RCM-SS six-relay control module provides an intelligent alarm system with six Form-C relays. The first module is addressed from 01 to 94 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normallyopen or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit. Each RCM-SS module has panelcontrolled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Features
* Six addressable Form-C relay contacts. * Removable 12 AWG (3.25 mm) to 18 AWG (0.9 mm) plug-in terminal blocks. * Status indicators for each point. * Unused addresses may be disabled. * Rotary address switches. * Compatible with Gamewell's 602, 610, 632, 654 and 658 FACPs with SmartScanTM SLC. * Mount one or two modules in a BB-XP cabinet (optional). * Mount up to six modules on a CHS-6 chassis in a BB-25 cabinet (optional). * Mounting hardware included.
Listings
Listings and approvals below apply to the RCM-SS Six-Relay Addressable Control Module. In some cases, the module may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. * UL Listed: file S521. * CSFM approved: file 7300-1288:169. * MEA approved: file 368-01-E Vol. II.
Product Line Information
RCM-SS: Six-relay control module. BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm) deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep overall. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep. CHS-6: Chassis, mounts up to six modules in a BB-25 cabinet.
RCM-SS CS-2469 10/25/04
Page 1 of 2
Specifications
Standby current 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases). Alarm current 32 mA (assumes all six relays have been switched once and all six LEDs solid ON). Temperature range 32F to 120F (0C to 49C). Humidity 10% to 85% noncondensing. Dimensions 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.0" (25.40 mm) deep. Shipping weight 1.1 lb. (0.499 kg) including packaging. Mounting options CHS-6 chassis, BB-25 cabinet. Relay current 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control. Relay contact ratings 30 VDC; 70.7 VAC. Current ratings * 3.0 A @ 30 VDC maximum, resistive, non-coded. * 2.0 A @ 30 VDC maximum, resistive, coded. * 1.0 A @ 30 VDC maximum, inductive (L/R = 2 ms), coded. * 0.5 A @ 30 VDC maximum, inductive (L/R = 5 ms), coded. * 0.9 A @ 110 VDC maximum, resistive, non-coded. * 0.9 A @ 125 VAC maximum, resistive, non-coded. * 0.7 A @ 70.7 VAC maximum, inductive (PF = 0.35), non-coded. * 0.5 A @ 125 VAC maximum, inductive (PF = 0.35), non-coded.
Wiring Diagram
6926wir1.wmf
Gamewell 12 Clintonville Road Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell.com A Honeywell Company (c) 2004 Gamewell
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell.
Page 2 of 2 RCM-SS CS-2469 10/25/04